Skip to content
Slide 1
Frequently Asked Questions
Image is not available

Frequently Asked Questions

General

The Department has commissioned some comparative testing of doors using these two standards. The conclusions of this work are that for the purposes of Item 2.d of Table B1(provisions for fire doors) of Approved Document B (Vol2), results from EN 81-58 tests can be accepted as equivalent to BS 476 part 22. In due course, the Department intends to publish the report from this work and amendments to the Approved Document necessary to meet the requirements of the Lifts Directive.

Many do accept this arrangement where they are satisfied that it will provide a sufficient level of protection to escape routes within dwellings. The Building Control Alliance Technical Guidance Note 9 provides further advice.

Increasing the period of fire resistance of the compartment walls between flats beyond that specified in the Approved Document is unlikely to have any significant impact on the safety of occupants of the building and would have no discernable benefit to persons in the flat where the fire has started.

It is estimated that the provision of a BS 9251 sprinkler system within a dwelling will reduce fire-related casualties by around 70%. Whilst it would be desirable to install such systems in all dwellings it was decided that it would only be reasonable to impose this on larger buildings.

This was following analysis of the costs and benefits in the research report: The effectiveness of sprinklers in residential premises and consideration of the increased hazards for fire-fighters and other persons associated with fires in tall buildings, as discussed in the Regulatory Impact Assessment: Changes to Part B (Fire Safety) of the Building Regulations 2000 (as amended) and Approved Document B.

The 30m trigger height is considered to be a logical provision which aligns with the provisions for sprinkler protection for other building uses.

There may be alternative fire suppression systems that could be used where it can be demonstrated that a similar level of performance as would be provided by a BS 9251 sprinkler system can be achieved.

Where water mist systems are proposed the guidance contained in the BRE publication An Independent Guide on Water Mist Systems for Residential Buildings may assist Building Control Bodies in assessing such systems.

Diagram 30a applies a more onerous standard than Diagram 30b, any combustible (including thermosetting) core panels should incorporate a band of material of limited combustibility 300mm wide centred over the wall.

However, an alternative approach might be to use a panel system which has been shown in a large-scale test to resist internal and external surface flaming and concealed burning.

In low-rise residential, office or assembly buildings to which Diagram 30b applies, panels with thermosetting cores can be used without any additional protection.

However, fire-stopping must be provided to seal the joint between the compartment wall and the underside of the panel. Any voids above the panel (such as where an additional roof covering is provided) should also be adequately fire-stopped.

No. Requirement B3(3) requires, where reasonably necessary, subdivision of the building with fire-resisting construction and/or the installation of a suitable automatic fire suppression system.

What is considered reasonable in any particular case will depend on the size and intended use of the building. In some cases, either sprinklers or compartment walls and floors will be necessary and other cases it may be necessary to provide both or neither. Guidance on where sprinklers should be provided is given the Approved Document.

Door closers are not required for internal fire doors in flats when they are being used to provide lobby protection for a common stair.

However, the requirement for the provision of fire-resisting doors remains as does the advice to householders that doors should be kept shut, especially at night.

Regulation 4 of the Building Regulations 2000 states that “building work” should comply with the applicable requirements contained in Schedule 1. Regulation 4(2)a then goes on to state that, “after the work is completed, the building as a whole should comply with the applicable requirements of Schedule 1 or, where the building did not previously comply with any such requirement, is no more unsatisfactory in relation to that requirement than before the work was carried out.”

Where an existing shop is extended such that the final floor area is greater than 2000m2 (whether it exceeded this value previously or not) then the building as a whole may be less satisfactory in relation to requirement B3(3) than before the work was carried out.

Therefore, the building would have to be either subdivided to limit the compartment size, fitted with sprinklers or some other solution would be necessary in order to satisfy regulation 4(2) in relation to requirement B3.

Regulation 4(2) must be judged against the requirements set out in Schedule 1 rather than the Approved Document. B3(3) requires sub-division of the building “to an extent appropriate” to its size and intended use and it may be that some buildings will still comply with B3(3) by virtue of its intended use even though they have been extended without further capitalisation.

This would be a matter for the designer and the relevant building control body to consider. However, any such proposal may result in the need to upgrade the specification of the sprinkler system and the duration of water supplies.

Provision of water supplies does not, on its own, reduce the physiological impact on firefighters of travelling long distances whilst carrying heavy equipment. Water from private hydrants may still need to be pumped before it can be used for firefighting.

Where it is proposed to adopt an alternative approach to meeting requirement B5 (Access and facilities for the fire service). It would be advisable to seek the advice of the fire and rescue service who can advise on the practicalities of fire fighting.

The vertical distance referred to in paragraph 2.16 c. should be measured from the entrance storey of the flat, not the entrance floor of the building.

Item 2 of Table 3 (Maximum nominal internal diameter of pipes passing through fire separating element) now makes it clear that a uPVC pipe, up to 110mm in diameter, can pass through a wall or floor separating a dwellinghouse from an integral garage. The pipe should, however, still be fire stopped in accordance with paragraph 7.8. This would involve sealing around the pipe where it penetrates the wall or floor using a suitable material or a proprietary system as described in Paragraph 7.14.

Guidance in both volumes of the Approved Document Part B states there should be vehicle access for a pump appliance to within 45m of all points within dwellings. This is to take account of the actual distance that the Fire & Rescue Service need to carry kit and lay hoses from the vehicle to a potential point of fire.

Guidance in both Volumes of the Approved Document Part B states there should be vehicle access for a pump appliance to within 45m of all points within dwellings. This is to take account of the actual distance that the fire fighters need to carry kit and lay hoses from the vehicle to reach a potential fire.

When an Approved Document refers to a named standard, the relevant version of the standard is the one listed at the end of the publication. However, if this version of the standard has been revised or updated by the issuing standards body, the new version may be used as a source of guidance provided it continues to address the relevant requirements of the Regulations.

Volume 2 of Approved Document B currently refers to the guidance in several of the BS 5588 series of standards as a means of showing compliance with the requirements of Part B (Fire safety) of Schedule 1 to the Building Regulations. Until such time as the Approved Document is amended, these references remain part of the guidance approved under section 6 of the 1984 Building Act. As such, compliance with the guidance referred to would confer a legal presumption of conformity with the relevant requirements of Part B.
Following any other guidance would not confer that legal presumption.

Where designers elect to follow the relevant guidance in BS 9999 they will need to satisfy themselves and the building control body that this guidance adequately addresses the requirements of Part B. It is strongly recommended in such cases that designers discuss their proposals with the building control body before starting work.

Withdrawn BS standards are readily available from:
The BSI Knowledge Centre
British Standards Institution
389 Chiswick High Road
London, W4 4AL
Email: knowledgecentre@bsigroup.com
Tel: +44 (0)20 8996 7004

The Housing Act 2004 replaced the previous housing fitness standard with a statutory framework for assessing and tackling hazards in housing – including fire hazards.

Within a house designated as a ‘House in Multiple Occupation’ such devices may still need to be provided between the private areas (ie bedrooms) and the common parts (ie circulation spaces, living room, kitchen etc).

No, this is a printing error. The word “over” should be retained as for the 2000 edition of Approved Document Part B, and so paragraph 9.12 of Volume 2 of Approved Document Part B 2006 should read: “Where the concealed space is over an undivided area which exceeds 40m (this may be in both directions on plan) there is no limit to the size of the cavity if…….”.

Cavity barriers are provided to reduce the risk from unseen fire spread within concealed spaces in accordance with requirement B3(4) of the Building Regulations. The principle of paragraph 9.12 is that it relates to a concealed space over a single undivided room (such as an open-plan office). Because the room below the space is undivided, the occupants will be able to see a fire develop and react to the changing hazard, thus cavity barriers within the space above are less important than with a cellular layout. The conditions in paragraph 9.12 are intended to reduce the risk of a fire starting/spreading in the undivided void and to prevent fire entering the void from outside the room which is not visible to its occupants.

For the purposes of Part B of the Building Regulations an LD3 system is considered to be adequate. The system itself should therefore be installed in accordance with the guidance for LD3 systems in BS 5839-6:2004.

For the purposes of Part B of the Building Regulations, an LD3 system is considered to be adequate. The system itself should, therefore, be installed in accordance with the guidance for LD3 systems in BS 5839- 6: 2004.

For the purposes of meeting the provisions of Paragraph 8.14, the limit on the scope of BS 9251 to buildings below 20m can be ignored. However, the other limits such as the number of sprinkler heads per room should be observed.

In blocks which are taller than 30m in height, all the individual flats throughout the building should be sprinklered. However, it would not be necessary to provide them in the common areas such as stairs, corridors or landings.

The guidance in B1 Section 1 of the Approved Document (fire alarm and fire detection systems) is not intended to be applied to the common parts of blocks of flats and does not include a provision to interconnect installations in separate flats.

Fire detection devices may need to be provided in some blocks to actuate automatic smoke control systems in the common parts of the building in accordance with paragraph 2.25. Such devices are not expected to be linked to a common alarm system.

A protected stairway should be enclosed with fire-resisting construction and fire resisting doors in order to protect people escaping down the stairs from a fire in the accommodation.

It may not always be necessary to provide fire doors on cupboards if they are small and the fire risk is low. An alternative to providing a fire door on a bathroom is to include the bathroom within the stair enclosure, thus removing the need for a fire door.

In many cases, premises which are similar to a family home can be designed in accordance with Volume 1 (Dwelling houses). However, such premises are subject to the Regulatory Reform (Fire Safety) Order 2005 and it may be necessary to take account of the duties imposed under that Order in the design of the premises.

The Department’s leaflet, Do You Have Paying Guests? provides some useful guidance on the application of the Fire Safety Order to B&Bs, guest houses and self-catering properties. Regardless of the design guidance that is adopted, it will still be necessary for Building Control Bodies to consult with Fire and Rescue Authorities on work relating to buildings where the Fire Safety Order is (or will be) applicable. This should ensure that any potential problems can be identified before building work is started.

Further guidance on the consultation process is given in the Department’s publication, Building Regulations and Fire Safety Procedural Guidance.

Our local Fire and Rescue Service appliances are fitted with hoses which are much longer than 45m.
The 45m criterion is based on the physiological demands on firefighters engaged in search and rescue and on the restrictions that may be imposed by their equipment.

When considering hose length it is important to appreciate that, in practice, hoses have a tendency to “snake” when charged thus limiting their effective length. It is also common practice to trim the ends of hoses where they become damaged. The time and effort it takes to lay out a hose may also be an important factor.

A fire-resisting door should be regarded as a complete installed assembly. Thus the door, the frame and any ironmongery should be considered when assessing its suitability. In most cases, however, it should be possible to retain the existing frame. If in doubt, the test report for the door being installed will include details of the door frame in which it was tested.

Fire doors are often thicker and much heavier than other internal doors. Where existing frames are retained it may be necessary to replace or relocate the door stops and to install additional fixings back to the structure. The joint between the frame and the surrounding structure should be adequately sealed and the operating gap between the door and the frame should be kept to a minimum (usually 3-4mm).

Technical

Part A - Structure

The Department has commissioned some comparative testing of doors using these two standards. The conclusions of this work are that for the purposes of Item 2.d of Table B1(provisions for fire doors) of Approved Document B (Vol2), results from EN 81-58 tests can be accepted as equivalent to BS 476 part 22. In due course, the Department intends to publish the report from this work and amendments to the Approved Document necessary to meet the requirements of the Lifts Directive.

Many do accept this arrangement where they are satisfied that it will provide a sufficient level of protection to escape routes within dwellings. The Building Control Alliance Technical Guidance Note 9 provides further advice.

Increasing the period of fire resistance of the compartment walls between flats beyond that specified in the Approved Document is unlikely to have any significant impact on the safety of occupants of the building and would have no discernable benefit to persons in the flat where the fire has started.

It is estimated that the provision of a BS 9251 sprinkler system within a dwelling will reduce fire-related casualties by around 70%. Whilst it would be desirable to install such systems in all dwellings it was decided that it would only be reasonable to impose this on larger buildings.

This was following analysis of the costs and benefits in the research report: The effectiveness of sprinklers in residential premises and consideration of the increased hazards for fire-fighters and other persons associated with fires in tall buildings, as discussed in the Regulatory Impact Assessment: Changes to Part B (Fire Safety) of the Building Regulations 2000 (as amended) and Approved Document B.

The 30m trigger height is considered to be a logical provision which aligns with the provisions for sprinkler protection for other building uses.

There may be alternative fire suppression systems that could be used where it can be demonstrated that a similar level of performance as would be provided by a BS 9251 sprinkler system can be achieved.

Where water mist systems are proposed the guidance contained in the BRE publication An Independent Guide on Water Mist Systems for Residential Buildings may assist Building Control Bodies in assessing such systems.

Diagram 30a applies a more onerous standard than Diagram 30b, any combustible (including thermosetting) core panels should incorporate a band of material of limited combustibility 300mm wide centred over the wall.

However, an alternative approach might be to use a panel system which has been shown in a large-scale test to resist internal and external surface flaming and concealed burning.

In low-rise residential, office or assembly buildings to which Diagram 30b applies, panels with thermosetting cores can be used without any additional protection.

However, fire-stopping must be provided to seal the joint between the compartment wall and the underside of the panel. Any voids above the panel (such as where an additional roof covering is provided) should also be adequately fire-stopped.

No. Requirement B3(3) requires, where reasonably necessary, subdivision of the building with fire-resisting construction and/or the installation of a suitable automatic fire suppression system.

What is considered reasonable in any particular case will depend on the size and intended use of the building. In some cases, either sprinklers or compartment walls and floors will be necessary and other cases it may be necessary to provide both or neither. Guidance on where sprinklers should be provided is given the Approved Document.

Door closers are not required for internal fire doors in flats when they are being used to provide lobby protection for a common stair.

However, the requirement for the provision of fire-resisting doors remains as does the advice to householders that doors should be kept shut, especially at night.

Regulation 4 of the Building Regulations 2000 states that “building work” should comply with the applicable requirements contained in Schedule 1. Regulation 4(2)a then goes on to state that, “after the work is completed, the building as a whole should comply with the applicable requirements of Schedule 1 or, where the building did not previously comply with any such requirement, is no more unsatisfactory in relation to that requirement than before the work was carried out.”

Where an existing shop is extended such that the final floor area is greater than 2000m2 (whether it exceeded this value previously or not) then the building as a whole may be less satisfactory in relation to requirement B3(3) than before the work was carried out.

Therefore, the building would have to be either subdivided to limit the compartment size, fitted with sprinklers or some other solution would be necessary in order to satisfy regulation 4(2) in relation to requirement B3.

Regulation 4(2) must be judged against the requirements set out in Schedule 1 rather than the Approved Document. B3(3) requires sub-division of the building “to an extent appropriate” to its size and intended use and it may be that some buildings will still comply with B3(3) by virtue of its intended use even though they have been extended without further capitalisation.

This would be a matter for the designer and the relevant building control body to consider. However, any such proposal may result in the need to upgrade the specification of the sprinkler system and the duration of water supplies.

Provision of water supplies does not, on its own, reduce the physiological impact on firefighters of travelling long distances whilst carrying heavy equipment. Water from private hydrants may still need to be pumped before it can be used for firefighting.

Where it is proposed to adopt an alternative approach to meeting requirement B5 (Access and facilities for the fire service). It would be advisable to seek the advice of the fire and rescue service who can advise on the practicalities of fire fighting.

The vertical distance referred to in paragraph 2.16 c. should be measured from the entrance storey of the flat, not the entrance floor of the building.

Item 2 of Table 3 (Maximum nominal internal diameter of pipes passing through fire separating element) now makes it clear that a uPVC pipe, up to 110mm in diameter, can pass through a wall or floor separating a dwellinghouse from an integral garage. The pipe should, however, still be fire stopped in accordance with paragraph 7.8. This would involve sealing around the pipe where it penetrates the wall or floor using a suitable material or a proprietary system as described in Paragraph 7.14.

Guidance in both volumes of the Approved Document Part B states there should be vehicle access for a pump appliance to within 45m of all points within dwellings. This is to take account of the actual distance that the Fire & Rescue Service need to carry kit and lay hoses from the vehicle to a potential point of fire.

Guidance in both Volumes of the Approved Document Part B states there should be vehicle access for a pump appliance to within 45m of all points within dwellings. This is to take account of the actual distance that the fire fighters need to carry kit and lay hoses from the vehicle to reach a potential fire.

When an Approved Document refers to a named standard, the relevant version of the standard is the one listed at the end of the publication. However, if this version of the standard has been revised or updated by the issuing standards body, the new version may be used as a source of guidance provided it continues to address the relevant requirements of the Regulations.

Volume 2 of Approved Document B currently refers to the guidance in several of the BS 5588 series of standards as a means of showing compliance with the requirements of Part B (Fire safety) of Schedule 1 to the Building Regulations. Until such time as the Approved Document is amended, these references remain part of the guidance approved under section 6 of the 1984 Building Act. As such, compliance with the guidance referred to would confer a legal presumption of conformity with the relevant requirements of Part B.
Following any other guidance would not confer that legal presumption.

Where designers elect to follow the relevant guidance in BS 9999 they will need to satisfy themselves and the building control body that this guidance adequately addresses the requirements of Part B. It is strongly recommended in such cases that designers discuss their proposals with the building control body before starting work.

Withdrawn BS standards are readily available from:
The BSI Knowledge Centre
British Standards Institution
389 Chiswick High Road
London, W4 4AL
Email: knowledgecentre@bsigroup.com
Tel: +44 (0)20 8996 7004

The Housing Act 2004 replaced the previous housing fitness standard with a statutory framework for assessing and tackling hazards in housing – including fire hazards.

Within a house designated as a ‘House in Multiple Occupation’ such devices may still need to be provided between the private areas (ie bedrooms) and the common parts (ie circulation spaces, living room, kitchen etc).

No, this is a printing error. The word “over” should be retained as for the 2000 edition of Approved Document Part B, and so paragraph 9.12 of Volume 2 of Approved Document Part B 2006 should read: “Where the concealed space is over an undivided area which exceeds 40m (this may be in both directions on plan) there is no limit to the size of the cavity if…….”.

Cavity barriers are provided to reduce the risk from unseen fire spread within concealed spaces in accordance with requirement B3(4) of the Building Regulations. The principle of paragraph 9.12 is that it relates to a concealed space over a single undivided room (such as an open-plan office). Because the room below the space is undivided, the occupants will be able to see a fire develop and react to the changing hazard, thus cavity barriers within the space above are less important than with a cellular layout. The conditions in paragraph 9.12 are intended to reduce the risk of a fire starting/spreading in the undivided void and to prevent fire entering the void from outside the room which is not visible to its occupants.

For the purposes of Part B of the Building Regulations an LD3 system is considered to be adequate. The system itself should therefore be installed in accordance with the guidance for LD3 systems in BS 5839-6:2004.

For the purposes of Part B of the Building Regulations, an LD3 system is considered to be adequate. The system itself should, therefore, be installed in accordance with the guidance for LD3 systems in BS 5839- 6: 2004.

For the purposes of meeting the provisions of Paragraph 8.14, the limit on the scope of BS 9251 to buildings below 20m can be ignored. However, the other limits such as the number of sprinkler heads per room should be observed.

In blocks which are taller than 30m in height, all the individual flats throughout the building should be sprinklered. However, it would not be necessary to provide them in the common areas such as stairs, corridors or landings.

The guidance in B1 Section 1 of the Approved Document (fire alarm and fire detection systems) is not intended to be applied to the common parts of blocks of flats and does not include a provision to interconnect installations in separate flats.

Fire detection devices may need to be provided in some blocks to actuate automatic smoke control systems in the common parts of the building in accordance with paragraph 2.25. Such devices are not expected to be linked to a common alarm system.

A protected stairway should be enclosed with fire-resisting construction and fire resisting doors in order to protect people escaping down the stairs from a fire in the accommodation.

It may not always be necessary to provide fire doors on cupboards if they are small and the fire risk is low. An alternative to providing a fire door on a bathroom is to include the bathroom within the stair enclosure, thus removing the need for a fire door.

In many cases, premises which are similar to a family home can be designed in accordance with Volume 1 (Dwelling houses). However, such premises are subject to the Regulatory Reform (Fire Safety) Order 2005 and it may be necessary to take account of the duties imposed under that Order in the design of the premises.

The Department’s leaflet, Do You Have Paying Guests? provides some useful guidance on the application of the Fire Safety Order to B&Bs, guest houses and self-catering properties. Regardless of the design guidance that is adopted, it will still be necessary for Building Control Bodies to consult with Fire and Rescue Authorities on work relating to buildings where the Fire Safety Order is (or will be) applicable. This should ensure that any potential problems can be identified before building work is started.

Further guidance on the consultation process is given in the Department’s publication, Building Regulations and Fire Safety Procedural Guidance.

Our local Fire and Rescue Service appliances are fitted with hoses which are much longer than 45m.
The 45m criterion is based on the physiological demands on firefighters engaged in search and rescue and on the restrictions that may be imposed by their equipment.

When considering hose length it is important to appreciate that, in practice, hoses have a tendency to “snake” when charged thus limiting their effective length. It is also common practice to trim the ends of hoses where they become damaged. The time and effort it takes to lay out a hose may also be an important factor.

A fire-resisting door should be regarded as a complete installed assembly. Thus the door, the frame and any ironmongery should be considered when assessing its suitability. In most cases, however, it should be possible to retain the existing frame. If in doubt, the test report for the door being installed will include details of the door frame in which it was tested.

Fire doors are often thicker and much heavier than other internal doors. Where existing frames are retained it may be necessary to replace or relocate the door stops and to install additional fixings back to the structure. The joint between the frame and the surrounding structure should be adequately sealed and the operating gap between the door and the frame should be kept to a minimum (usually 3-4mm).

Part B - Fire Safety

The Department has commissioned some comparative testing of doors using these two standards. The conclusions of this work are that for the purposes of Item 2.d of Table B1(provisions for fire doors) of Approved Document B (Vol2), results from EN 81-58 tests can be accepted as equivalent to BS 476 part 22. In due course, the Department intends to publish the report from this work and amendments to the Approved Document necessary to meet the requirements of the Lifts Directive.

Many do accept this arrangement where they are satisfied that it will provide a sufficient level of protection to escape routes within dwellings. The Building Control Alliance Technical Guidance Note 9 provides further advice.

Increasing the period of fire resistance of the compartment walls between flats beyond that specified in the Approved Document is unlikely to have any significant impact on the safety of occupants of the building and would have no discernable benefit to persons in the flat where the fire has started.

It is estimated that the provision of a BS 9251 sprinkler system within a dwelling will reduce fire-related casualties by around 70%. Whilst it would be desirable to install such systems in all dwellings it was decided that it would only be reasonable to impose this on larger buildings.

This was following analysis of the costs and benefits in the research report: The effectiveness of sprinklers in residential premises and consideration of the increased hazards for fire-fighters and other persons associated with fires in tall buildings, as discussed in the Regulatory Impact Assessment: Changes to Part B (Fire Safety) of the Building Regulations 2000 (as amended) and Approved Document B.

The 30m trigger height is considered to be a logical provision which aligns with the provisions for sprinkler protection for other building uses.

There may be alternative fire suppression systems that could be used where it can be demonstrated that a similar level of performance as would be provided by a BS 9251 sprinkler system can be achieved.

Where water mist systems are proposed the guidance contained in the BRE publication An Independent Guide on Water Mist Systems for Residential Buildings may assist Building Control Bodies in assessing such systems.

Diagram 30a applies a more onerous standard than Diagram 30b, any combustible (including thermosetting) core panels should incorporate a band of material of limited combustibility 300mm wide centred over the wall.

However, an alternative approach might be to use a panel system which has been shown in a large-scale test to resist internal and external surface flaming and concealed burning.

In low-rise residential, office or assembly buildings to which Diagram 30b applies, panels with thermosetting cores can be used without any additional protection.

However, fire-stopping must be provided to seal the joint between the compartment wall and the underside of the panel. Any voids above the panel (such as where an additional roof covering is provided) should also be adequately fire-stopped.

No. Requirement B3(3) requires, where reasonably necessary, subdivision of the building with fire-resisting construction and/or the installation of a suitable automatic fire suppression system.

What is considered reasonable in any particular case will depend on the size and intended use of the building. In some cases, either sprinklers or compartment walls and floors will be necessary and other cases it may be necessary to provide both or neither. Guidance on where sprinklers should be provided is given the Approved Document.

Door closers are not required for internal fire doors in flats when they are being used to provide lobby protection for a common stair.

However, the requirement for the provision of fire-resisting doors remains as does the advice to householders that doors should be kept shut, especially at night.

Regulation 4 of the Building Regulations 2000 states that “building work” should comply with the applicable requirements contained in Schedule 1. Regulation 4(2)a then goes on to state that, “after the work is completed, the building as a whole should comply with the applicable requirements of Schedule 1 or, where the building did not previously comply with any such requirement, is no more unsatisfactory in relation to that requirement than before the work was carried out.”

Where an existing shop is extended such that the final floor area is greater than 2000m2 (whether it exceeded this value previously or not) then the building as a whole may be less satisfactory in relation to requirement B3(3) than before the work was carried out.

Therefore, the building would have to be either subdivided to limit the compartment size, fitted with sprinklers or some other solution would be necessary in order to satisfy regulation 4(2) in relation to requirement B3.

Regulation 4(2) must be judged against the requirements set out in Schedule 1 rather than the Approved Document. B3(3) requires sub-division of the building “to an extent appropriate” to its size and intended use and it may be that some buildings will still comply with B3(3) by virtue of its intended use even though they have been extended without further capitalisation.

This would be a matter for the designer and the relevant building control body to consider. However, any such proposal may result in the need to upgrade the specification of the sprinkler system and the duration of water supplies.

Provision of water supplies does not, on its own, reduce the physiological impact on firefighters of travelling long distances whilst carrying heavy equipment. Water from private hydrants may still need to be pumped before it can be used for firefighting.

Where it is proposed to adopt an alternative approach to meeting requirement B5 (Access and facilities for the fire service). It would be advisable to seek the advice of the fire and rescue service who can advise on the practicalities of fire fighting.

The vertical distance referred to in paragraph 2.16 c. should be measured from the entrance storey of the flat, not the entrance floor of the building.

Item 2 of Table 3 (Maximum nominal internal diameter of pipes passing through fire separating element) now makes it clear that a uPVC pipe, up to 110mm in diameter, can pass through a wall or floor separating a dwellinghouse from an integral garage. The pipe should, however, still be fire stopped in accordance with paragraph 7.8. This would involve sealing around the pipe where it penetrates the wall or floor using a suitable material or a proprietary system as described in Paragraph 7.14.

Guidance in both volumes of the Approved Document Part B states there should be vehicle access for a pump appliance to within 45m of all points within dwellings. This is to take account of the actual distance that the Fire & Rescue Service need to carry kit and lay hoses from the vehicle to a potential point of fire.

Guidance in both Volumes of the Approved Document Part B states there should be vehicle access for a pump appliance to within 45m of all points within dwellings. This is to take account of the actual distance that the fire fighters need to carry kit and lay hoses from the vehicle to reach a potential fire.

When an Approved Document refers to a named standard, the relevant version of the standard is the one listed at the end of the publication. However, if this version of the standard has been revised or updated by the issuing standards body, the new version may be used as a source of guidance provided it continues to address the relevant requirements of the Regulations.

Volume 2 of Approved Document B currently refers to the guidance in several of the BS 5588 series of standards as a means of showing compliance with the requirements of Part B (Fire safety) of Schedule 1 to the Building Regulations. Until such time as the Approved Document is amended, these references remain part of the guidance approved under section 6 of the 1984 Building Act. As such, compliance with the guidance referred to would confer a legal presumption of conformity with the relevant requirements of Part B.
Following any other guidance would not confer that legal presumption.

Where designers elect to follow the relevant guidance in BS 9999 they will need to satisfy themselves and the building control body that this guidance adequately addresses the requirements of Part B. It is strongly recommended in such cases that designers discuss their proposals with the building control body before starting work.

Withdrawn BS standards are readily available from:
The BSI Knowledge Centre
British Standards Institution
389 Chiswick High Road
London, W4 4AL
Email: knowledgecentre@bsigroup.com
Tel: +44 (0)20 8996 7004

The Housing Act 2004 replaced the previous housing fitness standard with a statutory framework for assessing and tackling hazards in housing – including fire hazards.

Within a house designated as a ‘House in Multiple Occupation’ such devices may still need to be provided between the private areas (ie bedrooms) and the common parts (ie circulation spaces, living room, kitchen etc).

No, this is a printing error. The word “over” should be retained as for the 2000 edition of Approved Document Part B, and so paragraph 9.12 of Volume 2 of Approved Document Part B 2006 should read: “Where the concealed space is over an undivided area which exceeds 40m (this may be in both directions on plan) there is no limit to the size of the cavity if…….”.

Cavity barriers are provided to reduce the risk from unseen fire spread within concealed spaces in accordance with requirement B3(4) of the Building Regulations. The principle of paragraph 9.12 is that it relates to a concealed space over a single undivided room (such as an open-plan office). Because the room below the space is undivided, the occupants will be able to see a fire develop and react to the changing hazard, thus cavity barriers within the space above are less important than with a cellular layout. The conditions in paragraph 9.12 are intended to reduce the risk of a fire starting/spreading in the undivided void and to prevent fire entering the void from outside the room which is not visible to its occupants.

For the purposes of Part B of the Building Regulations an LD3 system is considered to be adequate. The system itself should therefore be installed in accordance with the guidance for LD3 systems in BS 5839-6:2004.

For the purposes of Part B of the Building Regulations, an LD3 system is considered to be adequate. The system itself should, therefore, be installed in accordance with the guidance for LD3 systems in BS 5839- 6: 2004.

For the purposes of meeting the provisions of Paragraph 8.14, the limit on the scope of BS 9251 to buildings below 20m can be ignored. However, the other limits such as the number of sprinkler heads per room should be observed.

In blocks which are taller than 30m in height, all the individual flats throughout the building should be sprinklered. However, it would not be necessary to provide them in the common areas such as stairs, corridors or landings.

The guidance in B1 Section 1 of the Approved Document (fire alarm and fire detection systems) is not intended to be applied to the common parts of blocks of flats and does not include a provision to interconnect installations in separate flats.

Fire detection devices may need to be provided in some blocks to actuate automatic smoke control systems in the common parts of the building in accordance with paragraph 2.25. Such devices are not expected to be linked to a common alarm system.

A protected stairway should be enclosed with fire-resisting construction and fire resisting doors in order to protect people escaping down the stairs from a fire in the accommodation.

It may not always be necessary to provide fire doors on cupboards if they are small and the fire risk is low. An alternative to providing a fire door on a bathroom is to include the bathroom within the stair enclosure, thus removing the need for a fire door.

In many cases, premises which are similar to a family home can be designed in accordance with Volume 1 (Dwelling houses). However, such premises are subject to the Regulatory Reform (Fire Safety) Order 2005 and it may be necessary to take account of the duties imposed under that Order in the design of the premises.

The Department’s leaflet, Do You Have Paying Guests? provides some useful guidance on the application of the Fire Safety Order to B&Bs, guest houses and self-catering properties. Regardless of the design guidance that is adopted, it will still be necessary for Building Control Bodies to consult with Fire and Rescue Authorities on work relating to buildings where the Fire Safety Order is (or will be) applicable. This should ensure that any potential problems can be identified before building work is started.

Further guidance on the consultation process is given in the Department’s publication, Building Regulations and Fire Safety Procedural Guidance.

Our local Fire and Rescue Service appliances are fitted with hoses which are much longer than 45m.
The 45m criterion is based on the physiological demands on firefighters engaged in search and rescue and on the restrictions that may be imposed by their equipment.

When considering hose length it is important to appreciate that, in practice, hoses have a tendency to “snake” when charged thus limiting their effective length. It is also common practice to trim the ends of hoses where they become damaged. The time and effort it takes to lay out a hose may also be an important factor.

A fire-resisting door should be regarded as a complete installed assembly. Thus the door, the frame and any ironmongery should be considered when assessing its suitability. In most cases, however, it should be possible to retain the existing frame. If in doubt, the test report for the door being installed will include details of the door frame in which it was tested.

Fire doors are often thicker and much heavier than other internal doors. Where existing frames are retained it may be necessary to replace or relocate the door stops and to install additional fixings back to the structure. The joint between the frame and the surrounding structure should be adequately sealed and the operating gap between the door and the frame should be kept to a minimum (usually 3-4mm).

Part C - Site preparation and resistance to contaminates and moisture

The Department has commissioned some comparative testing of doors using these two standards. The conclusions of this work are that for the purposes of Item 2.d of Table B1(provisions for fire doors) of Approved Document B (Vol2), results from EN 81-58 tests can be accepted as equivalent to BS 476 part 22. In due course, the Department intends to publish the report from this work and amendments to the Approved Document necessary to meet the requirements of the Lifts Directive.

Many do accept this arrangement where they are satisfied that it will provide a sufficient level of protection to escape routes within dwellings. The Building Control Alliance Technical Guidance Note 9 provides further advice.

Increasing the period of fire resistance of the compartment walls between flats beyond that specified in the Approved Document is unlikely to have any significant impact on the safety of occupants of the building and would have no discernable benefit to persons in the flat where the fire has started.

It is estimated that the provision of a BS 9251 sprinkler system within a dwelling will reduce fire-related casualties by around 70%. Whilst it would be desirable to install such systems in all dwellings it was decided that it would only be reasonable to impose this on larger buildings.

This was following analysis of the costs and benefits in the research report: The effectiveness of sprinklers in residential premises and consideration of the increased hazards for fire-fighters and other persons associated with fires in tall buildings, as discussed in the Regulatory Impact Assessment: Changes to Part B (Fire Safety) of the Building Regulations 2000 (as amended) and Approved Document B.

The 30m trigger height is considered to be a logical provision which aligns with the provisions for sprinkler protection for other building uses.

There may be alternative fire suppression systems that could be used where it can be demonstrated that a similar level of performance as would be provided by a BS 9251 sprinkler system can be achieved.

Where water mist systems are proposed the guidance contained in the BRE publication An Independent Guide on Water Mist Systems for Residential Buildings may assist Building Control Bodies in assessing such systems.

Diagram 30a applies a more onerous standard than Diagram 30b, any combustible (including thermosetting) core panels should incorporate a band of material of limited combustibility 300mm wide centred over the wall.

However, an alternative approach might be to use a panel system which has been shown in a large-scale test to resist internal and external surface flaming and concealed burning.

In low-rise residential, office or assembly buildings to which Diagram 30b applies, panels with thermosetting cores can be used without any additional protection.

However, fire-stopping must be provided to seal the joint between the compartment wall and the underside of the panel. Any voids above the panel (such as where an additional roof covering is provided) should also be adequately fire-stopped.

No. Requirement B3(3) requires, where reasonably necessary, subdivision of the building with fire-resisting construction and/or the installation of a suitable automatic fire suppression system.

What is considered reasonable in any particular case will depend on the size and intended use of the building. In some cases, either sprinklers or compartment walls and floors will be necessary and other cases it may be necessary to provide both or neither. Guidance on where sprinklers should be provided is given the Approved Document.

Door closers are not required for internal fire doors in flats when they are being used to provide lobby protection for a common stair.

However, the requirement for the provision of fire-resisting doors remains as does the advice to householders that doors should be kept shut, especially at night.

Regulation 4 of the Building Regulations 2000 states that “building work” should comply with the applicable requirements contained in Schedule 1. Regulation 4(2)a then goes on to state that, “after the work is completed, the building as a whole should comply with the applicable requirements of Schedule 1 or, where the building did not previously comply with any such requirement, is no more unsatisfactory in relation to that requirement than before the work was carried out.”

Where an existing shop is extended such that the final floor area is greater than 2000m2 (whether it exceeded this value previously or not) then the building as a whole may be less satisfactory in relation to requirement B3(3) than before the work was carried out.

Therefore, the building would have to be either subdivided to limit the compartment size, fitted with sprinklers or some other solution would be necessary in order to satisfy regulation 4(2) in relation to requirement B3.

Regulation 4(2) must be judged against the requirements set out in Schedule 1 rather than the Approved Document. B3(3) requires sub-division of the building “to an extent appropriate” to its size and intended use and it may be that some buildings will still comply with B3(3) by virtue of its intended use even though they have been extended without further capitalisation.

This would be a matter for the designer and the relevant building control body to consider. However, any such proposal may result in the need to upgrade the specification of the sprinkler system and the duration of water supplies.

Provision of water supplies does not, on its own, reduce the physiological impact on firefighters of travelling long distances whilst carrying heavy equipment. Water from private hydrants may still need to be pumped before it can be used for firefighting.

Where it is proposed to adopt an alternative approach to meeting requirement B5 (Access and facilities for the fire service). It would be advisable to seek the advice of the fire and rescue service who can advise on the practicalities of fire fighting.

The vertical distance referred to in paragraph 2.16 c. should be measured from the entrance storey of the flat, not the entrance floor of the building.

Item 2 of Table 3 (Maximum nominal internal diameter of pipes passing through fire separating element) now makes it clear that a uPVC pipe, up to 110mm in diameter, can pass through a wall or floor separating a dwellinghouse from an integral garage. The pipe should, however, still be fire stopped in accordance with paragraph 7.8. This would involve sealing around the pipe where it penetrates the wall or floor using a suitable material or a proprietary system as described in Paragraph 7.14.

Guidance in both volumes of the Approved Document Part B states there should be vehicle access for a pump appliance to within 45m of all points within dwellings. This is to take account of the actual distance that the Fire & Rescue Service need to carry kit and lay hoses from the vehicle to a potential point of fire.

Guidance in both Volumes of the Approved Document Part B states there should be vehicle access for a pump appliance to within 45m of all points within dwellings. This is to take account of the actual distance that the fire fighters need to carry kit and lay hoses from the vehicle to reach a potential fire.

When an Approved Document refers to a named standard, the relevant version of the standard is the one listed at the end of the publication. However, if this version of the standard has been revised or updated by the issuing standards body, the new version may be used as a source of guidance provided it continues to address the relevant requirements of the Regulations.

Volume 2 of Approved Document B currently refers to the guidance in several of the BS 5588 series of standards as a means of showing compliance with the requirements of Part B (Fire safety) of Schedule 1 to the Building Regulations. Until such time as the Approved Document is amended, these references remain part of the guidance approved under section 6 of the 1984 Building Act. As such, compliance with the guidance referred to would confer a legal presumption of conformity with the relevant requirements of Part B.
Following any other guidance would not confer that legal presumption.

Where designers elect to follow the relevant guidance in BS 9999 they will need to satisfy themselves and the building control body that this guidance adequately addresses the requirements of Part B. It is strongly recommended in such cases that designers discuss their proposals with the building control body before starting work.

Withdrawn BS standards are readily available from:
The BSI Knowledge Centre
British Standards Institution
389 Chiswick High Road
London, W4 4AL
Email: knowledgecentre@bsigroup.com
Tel: +44 (0)20 8996 7004

The Housing Act 2004 replaced the previous housing fitness standard with a statutory framework for assessing and tackling hazards in housing – including fire hazards.

Within a house designated as a ‘House in Multiple Occupation’ such devices may still need to be provided between the private areas (ie bedrooms) and the common parts (ie circulation spaces, living room, kitchen etc).

No, this is a printing error. The word “over” should be retained as for the 2000 edition of Approved Document Part B, and so paragraph 9.12 of Volume 2 of Approved Document Part B 2006 should read: “Where the concealed space is over an undivided area which exceeds 40m (this may be in both directions on plan) there is no limit to the size of the cavity if…….”.

Cavity barriers are provided to reduce the risk from unseen fire spread within concealed spaces in accordance with requirement B3(4) of the Building Regulations. The principle of paragraph 9.12 is that it relates to a concealed space over a single undivided room (such as an open-plan office). Because the room below the space is undivided, the occupants will be able to see a fire develop and react to the changing hazard, thus cavity barriers within the space above are less important than with a cellular layout. The conditions in paragraph 9.12 are intended to reduce the risk of a fire starting/spreading in the undivided void and to prevent fire entering the void from outside the room which is not visible to its occupants.

For the purposes of Part B of the Building Regulations an LD3 system is considered to be adequate. The system itself should therefore be installed in accordance with the guidance for LD3 systems in BS 5839-6:2004.

For the purposes of Part B of the Building Regulations, an LD3 system is considered to be adequate. The system itself should, therefore, be installed in accordance with the guidance for LD3 systems in BS 5839- 6: 2004.

For the purposes of meeting the provisions of Paragraph 8.14, the limit on the scope of BS 9251 to buildings below 20m can be ignored. However, the other limits such as the number of sprinkler heads per room should be observed.

In blocks which are taller than 30m in height, all the individual flats throughout the building should be sprinklered. However, it would not be necessary to provide them in the common areas such as stairs, corridors or landings.

The guidance in B1 Section 1 of the Approved Document (fire alarm and fire detection systems) is not intended to be applied to the common parts of blocks of flats and does not include a provision to interconnect installations in separate flats.

Fire detection devices may need to be provided in some blocks to actuate automatic smoke control systems in the common parts of the building in accordance with paragraph 2.25. Such devices are not expected to be linked to a common alarm system.

A protected stairway should be enclosed with fire-resisting construction and fire resisting doors in order to protect people escaping down the stairs from a fire in the accommodation.

It may not always be necessary to provide fire doors on cupboards if they are small and the fire risk is low. An alternative to providing a fire door on a bathroom is to include the bathroom within the stair enclosure, thus removing the need for a fire door.

In many cases, premises which are similar to a family home can be designed in accordance with Volume 1 (Dwelling houses). However, such premises are subject to the Regulatory Reform (Fire Safety) Order 2005 and it may be necessary to take account of the duties imposed under that Order in the design of the premises.

The Department’s leaflet, Do You Have Paying Guests? provides some useful guidance on the application of the Fire Safety Order to B&Bs, guest houses and self-catering properties. Regardless of the design guidance that is adopted, it will still be necessary for Building Control Bodies to consult with Fire and Rescue Authorities on work relating to buildings where the Fire Safety Order is (or will be) applicable. This should ensure that any potential problems can be identified before building work is started.

Further guidance on the consultation process is given in the Department’s publication, Building Regulations and Fire Safety Procedural Guidance.

Our local Fire and Rescue Service appliances are fitted with hoses which are much longer than 45m.
The 45m criterion is based on the physiological demands on firefighters engaged in search and rescue and on the restrictions that may be imposed by their equipment.

When considering hose length it is important to appreciate that, in practice, hoses have a tendency to “snake” when charged thus limiting their effective length. It is also common practice to trim the ends of hoses where they become damaged. The time and effort it takes to lay out a hose may also be an important factor.

A fire-resisting door should be regarded as a complete installed assembly. Thus the door, the frame and any ironmongery should be considered when assessing its suitability. In most cases, however, it should be possible to retain the existing frame. If in doubt, the test report for the door being installed will include details of the door frame in which it was tested.

Fire doors are often thicker and much heavier than other internal doors. Where existing frames are retained it may be necessary to replace or relocate the door stops and to install additional fixings back to the structure. The joint between the frame and the surrounding structure should be adequately sealed and the operating gap between the door and the frame should be kept to a minimum (usually 3-4mm).

Part E - Resistance to the passage of sound

The Department has commissioned some comparative testing of doors using these two standards. The conclusions of this work are that for the purposes of Item 2.d of Table B1(provisions for fire doors) of Approved Document B (Vol2), results from EN 81-58 tests can be accepted as equivalent to BS 476 part 22. In due course, the Department intends to publish the report from this work and amendments to the Approved Document necessary to meet the requirements of the Lifts Directive.

Many do accept this arrangement where they are satisfied that it will provide a sufficient level of protection to escape routes within dwellings. The Building Control Alliance Technical Guidance Note 9 provides further advice.

Increasing the period of fire resistance of the compartment walls between flats beyond that specified in the Approved Document is unlikely to have any significant impact on the safety of occupants of the building and would have no discernable benefit to persons in the flat where the fire has started.

It is estimated that the provision of a BS 9251 sprinkler system within a dwelling will reduce fire-related casualties by around 70%. Whilst it would be desirable to install such systems in all dwellings it was decided that it would only be reasonable to impose this on larger buildings.

This was following analysis of the costs and benefits in the research report: The effectiveness of sprinklers in residential premises and consideration of the increased hazards for fire-fighters and other persons associated with fires in tall buildings, as discussed in the Regulatory Impact Assessment: Changes to Part B (Fire Safety) of the Building Regulations 2000 (as amended) and Approved Document B.

The 30m trigger height is considered to be a logical provision which aligns with the provisions for sprinkler protection for other building uses.

There may be alternative fire suppression systems that could be used where it can be demonstrated that a similar level of performance as would be provided by a BS 9251 sprinkler system can be achieved.

Where water mist systems are proposed the guidance contained in the BRE publication An Independent Guide on Water Mist Systems for Residential Buildings may assist Building Control Bodies in assessing such systems.

Diagram 30a applies a more onerous standard than Diagram 30b, any combustible (including thermosetting) core panels should incorporate a band of material of limited combustibility 300mm wide centred over the wall.

However, an alternative approach might be to use a panel system which has been shown in a large-scale test to resist internal and external surface flaming and concealed burning.

In low-rise residential, office or assembly buildings to which Diagram 30b applies, panels with thermosetting cores can be used without any additional protection.

However, fire-stopping must be provided to seal the joint between the compartment wall and the underside of the panel. Any voids above the panel (such as where an additional roof covering is provided) should also be adequately fire-stopped.

No. Requirement B3(3) requires, where reasonably necessary, subdivision of the building with fire-resisting construction and/or the installation of a suitable automatic fire suppression system.

What is considered reasonable in any particular case will depend on the size and intended use of the building. In some cases, either sprinklers or compartment walls and floors will be necessary and other cases it may be necessary to provide both or neither. Guidance on where sprinklers should be provided is given the Approved Document.

Door closers are not required for internal fire doors in flats when they are being used to provide lobby protection for a common stair.

However, the requirement for the provision of fire-resisting doors remains as does the advice to householders that doors should be kept shut, especially at night.

Regulation 4 of the Building Regulations 2000 states that “building work” should comply with the applicable requirements contained in Schedule 1. Regulation 4(2)a then goes on to state that, “after the work is completed, the building as a whole should comply with the applicable requirements of Schedule 1 or, where the building did not previously comply with any such requirement, is no more unsatisfactory in relation to that requirement than before the work was carried out.”

Where an existing shop is extended such that the final floor area is greater than 2000m2 (whether it exceeded this value previously or not) then the building as a whole may be less satisfactory in relation to requirement B3(3) than before the work was carried out.

Therefore, the building would have to be either subdivided to limit the compartment size, fitted with sprinklers or some other solution would be necessary in order to satisfy regulation 4(2) in relation to requirement B3.

Regulation 4(2) must be judged against the requirements set out in Schedule 1 rather than the Approved Document. B3(3) requires sub-division of the building “to an extent appropriate” to its size and intended use and it may be that some buildings will still comply with B3(3) by virtue of its intended use even though they have been extended without further capitalisation.

This would be a matter for the designer and the relevant building control body to consider. However, any such proposal may result in the need to upgrade the specification of the sprinkler system and the duration of water supplies.

Provision of water supplies does not, on its own, reduce the physiological impact on firefighters of travelling long distances whilst carrying heavy equipment. Water from private hydrants may still need to be pumped before it can be used for firefighting.

Where it is proposed to adopt an alternative approach to meeting requirement B5 (Access and facilities for the fire service). It would be advisable to seek the advice of the fire and rescue service who can advise on the practicalities of fire fighting.

The vertical distance referred to in paragraph 2.16 c. should be measured from the entrance storey of the flat, not the entrance floor of the building.

Item 2 of Table 3 (Maximum nominal internal diameter of pipes passing through fire separating element) now makes it clear that a uPVC pipe, up to 110mm in diameter, can pass through a wall or floor separating a dwellinghouse from an integral garage. The pipe should, however, still be fire stopped in accordance with paragraph 7.8. This would involve sealing around the pipe where it penetrates the wall or floor using a suitable material or a proprietary system as described in Paragraph 7.14.

Guidance in both volumes of the Approved Document Part B states there should be vehicle access for a pump appliance to within 45m of all points within dwellings. This is to take account of the actual distance that the Fire & Rescue Service need to carry kit and lay hoses from the vehicle to a potential point of fire.

Guidance in both Volumes of the Approved Document Part B states there should be vehicle access for a pump appliance to within 45m of all points within dwellings. This is to take account of the actual distance that the fire fighters need to carry kit and lay hoses from the vehicle to reach a potential fire.

When an Approved Document refers to a named standard, the relevant version of the standard is the one listed at the end of the publication. However, if this version of the standard has been revised or updated by the issuing standards body, the new version may be used as a source of guidance provided it continues to address the relevant requirements of the Regulations.

Volume 2 of Approved Document B currently refers to the guidance in several of the BS 5588 series of standards as a means of showing compliance with the requirements of Part B (Fire safety) of Schedule 1 to the Building Regulations. Until such time as the Approved Document is amended, these references remain part of the guidance approved under section 6 of the 1984 Building Act. As such, compliance with the guidance referred to would confer a legal presumption of conformity with the relevant requirements of Part B.
Following any other guidance would not confer that legal presumption.

Where designers elect to follow the relevant guidance in BS 9999 they will need to satisfy themselves and the building control body that this guidance adequately addresses the requirements of Part B. It is strongly recommended in such cases that designers discuss their proposals with the building control body before starting work.

Withdrawn BS standards are readily available from:
The BSI Knowledge Centre
British Standards Institution
389 Chiswick High Road
London, W4 4AL
Email: knowledgecentre@bsigroup.com
Tel: +44 (0)20 8996 7004

The Housing Act 2004 replaced the previous housing fitness standard with a statutory framework for assessing and tackling hazards in housing – including fire hazards.

Within a house designated as a ‘House in Multiple Occupation’ such devices may still need to be provided between the private areas (ie bedrooms) and the common parts (ie circulation spaces, living room, kitchen etc).

No, this is a printing error. The word “over” should be retained as for the 2000 edition of Approved Document Part B, and so paragraph 9.12 of Volume 2 of Approved Document Part B 2006 should read: “Where the concealed space is over an undivided area which exceeds 40m (this may be in both directions on plan) there is no limit to the size of the cavity if…….”.

Cavity barriers are provided to reduce the risk from unseen fire spread within concealed spaces in accordance with requirement B3(4) of the Building Regulations. The principle of paragraph 9.12 is that it relates to a concealed space over a single undivided room (such as an open-plan office). Because the room below the space is undivided, the occupants will be able to see a fire develop and react to the changing hazard, thus cavity barriers within the space above are less important than with a cellular layout. The conditions in paragraph 9.12 are intended to reduce the risk of a fire starting/spreading in the undivided void and to prevent fire entering the void from outside the room which is not visible to its occupants.

For the purposes of Part B of the Building Regulations an LD3 system is considered to be adequate. The system itself should therefore be installed in accordance with the guidance for LD3 systems in BS 5839-6:2004.

For the purposes of Part B of the Building Regulations, an LD3 system is considered to be adequate. The system itself should, therefore, be installed in accordance with the guidance for LD3 systems in BS 5839- 6: 2004.

For the purposes of meeting the provisions of Paragraph 8.14, the limit on the scope of BS 9251 to buildings below 20m can be ignored. However, the other limits such as the number of sprinkler heads per room should be observed.

In blocks which are taller than 30m in height, all the individual flats throughout the building should be sprinklered. However, it would not be necessary to provide them in the common areas such as stairs, corridors or landings.

The guidance in B1 Section 1 of the Approved Document (fire alarm and fire detection systems) is not intended to be applied to the common parts of blocks of flats and does not include a provision to interconnect installations in separate flats.

Fire detection devices may need to be provided in some blocks to actuate automatic smoke control systems in the common parts of the building in accordance with paragraph 2.25. Such devices are not expected to be linked to a common alarm system.

A protected stairway should be enclosed with fire-resisting construction and fire resisting doors in order to protect people escaping down the stairs from a fire in the accommodation.

It may not always be necessary to provide fire doors on cupboards if they are small and the fire risk is low. An alternative to providing a fire door on a bathroom is to include the bathroom within the stair enclosure, thus removing the need for a fire door.

In many cases, premises which are similar to a family home can be designed in accordance with Volume 1 (Dwelling houses). However, such premises are subject to the Regulatory Reform (Fire Safety) Order 2005 and it may be necessary to take account of the duties imposed under that Order in the design of the premises.

The Department’s leaflet, Do You Have Paying Guests? provides some useful guidance on the application of the Fire Safety Order to B&Bs, guest houses and self-catering properties. Regardless of the design guidance that is adopted, it will still be necessary for Building Control Bodies to consult with Fire and Rescue Authorities on work relating to buildings where the Fire Safety Order is (or will be) applicable. This should ensure that any potential problems can be identified before building work is started.

Further guidance on the consultation process is given in the Department’s publication, Building Regulations and Fire Safety Procedural Guidance.

Our local Fire and Rescue Service appliances are fitted with hoses which are much longer than 45m.
The 45m criterion is based on the physiological demands on firefighters engaged in search and rescue and on the restrictions that may be imposed by their equipment.

When considering hose length it is important to appreciate that, in practice, hoses have a tendency to “snake” when charged thus limiting their effective length. It is also common practice to trim the ends of hoses where they become damaged. The time and effort it takes to lay out a hose may also be an important factor.

A fire-resisting door should be regarded as a complete installed assembly. Thus the door, the frame and any ironmongery should be considered when assessing its suitability. In most cases, however, it should be possible to retain the existing frame. If in doubt, the test report for the door being installed will include details of the door frame in which it was tested.

Fire doors are often thicker and much heavier than other internal doors. Where existing frames are retained it may be necessary to replace or relocate the door stops and to install additional fixings back to the structure. The joint between the frame and the surrounding structure should be adequately sealed and the operating gap between the door and the frame should be kept to a minimum (usually 3-4mm).

Part G - Sanitation, hot water safety and water efficiency

The Department has commissioned some comparative testing of doors using these two standards. The conclusions of this work are that for the purposes of Item 2.d of Table B1(provisions for fire doors) of Approved Document B (Vol2), results from EN 81-58 tests can be accepted as equivalent to BS 476 part 22. In due course, the Department intends to publish the report from this work and amendments to the Approved Document necessary to meet the requirements of the Lifts Directive.

Many do accept this arrangement where they are satisfied that it will provide a sufficient level of protection to escape routes within dwellings. The Building Control Alliance Technical Guidance Note 9 provides further advice.

Increasing the period of fire resistance of the compartment walls between flats beyond that specified in the Approved Document is unlikely to have any significant impact on the safety of occupants of the building and would have no discernable benefit to persons in the flat where the fire has started.

It is estimated that the provision of a BS 9251 sprinkler system within a dwelling will reduce fire-related casualties by around 70%. Whilst it would be desirable to install such systems in all dwellings it was decided that it would only be reasonable to impose this on larger buildings.

This was following analysis of the costs and benefits in the research report: The effectiveness of sprinklers in residential premises and consideration of the increased hazards for fire-fighters and other persons associated with fires in tall buildings, as discussed in the Regulatory Impact Assessment: Changes to Part B (Fire Safety) of the Building Regulations 2000 (as amended) and Approved Document B.

The 30m trigger height is considered to be a logical provision which aligns with the provisions for sprinkler protection for other building uses.

There may be alternative fire suppression systems that could be used where it can be demonstrated that a similar level of performance as would be provided by a BS 9251 sprinkler system can be achieved.

Where water mist systems are proposed the guidance contained in the BRE publication An Independent Guide on Water Mist Systems for Residential Buildings may assist Building Control Bodies in assessing such systems.

Diagram 30a applies a more onerous standard than Diagram 30b, any combustible (including thermosetting) core panels should incorporate a band of material of limited combustibility 300mm wide centred over the wall.

However, an alternative approach might be to use a panel system which has been shown in a large-scale test to resist internal and external surface flaming and concealed burning.

In low-rise residential, office or assembly buildings to which Diagram 30b applies, panels with thermosetting cores can be used without any additional protection.

However, fire-stopping must be provided to seal the joint between the compartment wall and the underside of the panel. Any voids above the panel (such as where an additional roof covering is provided) should also be adequately fire-stopped.

No. Requirement B3(3) requires, where reasonably necessary, subdivision of the building with fire-resisting construction and/or the installation of a suitable automatic fire suppression system.

What is considered reasonable in any particular case will depend on the size and intended use of the building. In some cases, either sprinklers or compartment walls and floors will be necessary and other cases it may be necessary to provide both or neither. Guidance on where sprinklers should be provided is given the Approved Document.

Door closers are not required for internal fire doors in flats when they are being used to provide lobby protection for a common stair.

However, the requirement for the provision of fire-resisting doors remains as does the advice to householders that doors should be kept shut, especially at night.

Regulation 4 of the Building Regulations 2000 states that “building work” should comply with the applicable requirements contained in Schedule 1. Regulation 4(2)a then goes on to state that, “after the work is completed, the building as a whole should comply with the applicable requirements of Schedule 1 or, where the building did not previously comply with any such requirement, is no more unsatisfactory in relation to that requirement than before the work was carried out.”

Where an existing shop is extended such that the final floor area is greater than 2000m2 (whether it exceeded this value previously or not) then the building as a whole may be less satisfactory in relation to requirement B3(3) than before the work was carried out.

Therefore, the building would have to be either subdivided to limit the compartment size, fitted with sprinklers or some other solution would be necessary in order to satisfy regulation 4(2) in relation to requirement B3.

Regulation 4(2) must be judged against the requirements set out in Schedule 1 rather than the Approved Document. B3(3) requires sub-division of the building “to an extent appropriate” to its size and intended use and it may be that some buildings will still comply with B3(3) by virtue of its intended use even though they have been extended without further capitalisation.

This would be a matter for the designer and the relevant building control body to consider. However, any such proposal may result in the need to upgrade the specification of the sprinkler system and the duration of water supplies.

Provision of water supplies does not, on its own, reduce the physiological impact on firefighters of travelling long distances whilst carrying heavy equipment. Water from private hydrants may still need to be pumped before it can be used for firefighting.

Where it is proposed to adopt an alternative approach to meeting requirement B5 (Access and facilities for the fire service). It would be advisable to seek the advice of the fire and rescue service who can advise on the practicalities of fire fighting.

The vertical distance referred to in paragraph 2.16 c. should be measured from the entrance storey of the flat, not the entrance floor of the building.

Item 2 of Table 3 (Maximum nominal internal diameter of pipes passing through fire separating element) now makes it clear that a uPVC pipe, up to 110mm in diameter, can pass through a wall or floor separating a dwellinghouse from an integral garage. The pipe should, however, still be fire stopped in accordance with paragraph 7.8. This would involve sealing around the pipe where it penetrates the wall or floor using a suitable material or a proprietary system as described in Paragraph 7.14.

Guidance in both volumes of the Approved Document Part B states there should be vehicle access for a pump appliance to within 45m of all points within dwellings. This is to take account of the actual distance that the Fire & Rescue Service need to carry kit and lay hoses from the vehicle to a potential point of fire.

Guidance in both Volumes of the Approved Document Part B states there should be vehicle access for a pump appliance to within 45m of all points within dwellings. This is to take account of the actual distance that the fire fighters need to carry kit and lay hoses from the vehicle to reach a potential fire.

When an Approved Document refers to a named standard, the relevant version of the standard is the one listed at the end of the publication. However, if this version of the standard has been revised or updated by the issuing standards body, the new version may be used as a source of guidance provided it continues to address the relevant requirements of the Regulations.

Volume 2 of Approved Document B currently refers to the guidance in several of the BS 5588 series of standards as a means of showing compliance with the requirements of Part B (Fire safety) of Schedule 1 to the Building Regulations. Until such time as the Approved Document is amended, these references remain part of the guidance approved under section 6 of the 1984 Building Act. As such, compliance with the guidance referred to would confer a legal presumption of conformity with the relevant requirements of Part B.
Following any other guidance would not confer that legal presumption.

Where designers elect to follow the relevant guidance in BS 9999 they will need to satisfy themselves and the building control body that this guidance adequately addresses the requirements of Part B. It is strongly recommended in such cases that designers discuss their proposals with the building control body before starting work.

Withdrawn BS standards are readily available from:
The BSI Knowledge Centre
British Standards Institution
389 Chiswick High Road
London, W4 4AL
Email: knowledgecentre@bsigroup.com
Tel: +44 (0)20 8996 7004

The Housing Act 2004 replaced the previous housing fitness standard with a statutory framework for assessing and tackling hazards in housing – including fire hazards.

Within a house designated as a ‘House in Multiple Occupation’ such devices may still need to be provided between the private areas (ie bedrooms) and the common parts (ie circulation spaces, living room, kitchen etc).

No, this is a printing error. The word “over” should be retained as for the 2000 edition of Approved Document Part B, and so paragraph 9.12 of Volume 2 of Approved Document Part B 2006 should read: “Where the concealed space is over an undivided area which exceeds 40m (this may be in both directions on plan) there is no limit to the size of the cavity if…….”.

Cavity barriers are provided to reduce the risk from unseen fire spread within concealed spaces in accordance with requirement B3(4) of the Building Regulations. The principle of paragraph 9.12 is that it relates to a concealed space over a single undivided room (such as an open-plan office). Because the room below the space is undivided, the occupants will be able to see a fire develop and react to the changing hazard, thus cavity barriers within the space above are less important than with a cellular layout. The conditions in paragraph 9.12 are intended to reduce the risk of a fire starting/spreading in the undivided void and to prevent fire entering the void from outside the room which is not visible to its occupants.

For the purposes of Part B of the Building Regulations an LD3 system is considered to be adequate. The system itself should therefore be installed in accordance with the guidance for LD3 systems in BS 5839-6:2004.

For the purposes of Part B of the Building Regulations, an LD3 system is considered to be adequate. The system itself should, therefore, be installed in accordance with the guidance for LD3 systems in BS 5839- 6: 2004.

For the purposes of meeting the provisions of Paragraph 8.14, the limit on the scope of BS 9251 to buildings below 20m can be ignored. However, the other limits such as the number of sprinkler heads per room should be observed.

In blocks which are taller than 30m in height, all the individual flats throughout the building should be sprinklered. However, it would not be necessary to provide them in the common areas such as stairs, corridors or landings.

The guidance in B1 Section 1 of the Approved Document (fire alarm and fire detection systems) is not intended to be applied to the common parts of blocks of flats and does not include a provision to interconnect installations in separate flats.

Fire detection devices may need to be provided in some blocks to actuate automatic smoke control systems in the common parts of the building in accordance with paragraph 2.25. Such devices are not expected to be linked to a common alarm system.

A protected stairway should be enclosed with fire-resisting construction and fire resisting doors in order to protect people escaping down the stairs from a fire in the accommodation.

It may not always be necessary to provide fire doors on cupboards if they are small and the fire risk is low. An alternative to providing a fire door on a bathroom is to include the bathroom within the stair enclosure, thus removing the need for a fire door.

In many cases, premises which are similar to a family home can be designed in accordance with Volume 1 (Dwelling houses). However, such premises are subject to the Regulatory Reform (Fire Safety) Order 2005 and it may be necessary to take account of the duties imposed under that Order in the design of the premises.

The Department’s leaflet, Do You Have Paying Guests? provides some useful guidance on the application of the Fire Safety Order to B&Bs, guest houses and self-catering properties. Regardless of the design guidance that is adopted, it will still be necessary for Building Control Bodies to consult with Fire and Rescue Authorities on work relating to buildings where the Fire Safety Order is (or will be) applicable. This should ensure that any potential problems can be identified before building work is started.

Further guidance on the consultation process is given in the Department’s publication, Building Regulations and Fire Safety Procedural Guidance.

Our local Fire and Rescue Service appliances are fitted with hoses which are much longer than 45m.
The 45m criterion is based on the physiological demands on firefighters engaged in search and rescue and on the restrictions that may be imposed by their equipment.

When considering hose length it is important to appreciate that, in practice, hoses have a tendency to “snake” when charged thus limiting their effective length. It is also common practice to trim the ends of hoses where they become damaged. The time and effort it takes to lay out a hose may also be an important factor.

A fire-resisting door should be regarded as a complete installed assembly. Thus the door, the frame and any ironmongery should be considered when assessing its suitability. In most cases, however, it should be possible to retain the existing frame. If in doubt, the test report for the door being installed will include details of the door frame in which it was tested.

Fire doors are often thicker and much heavier than other internal doors. Where existing frames are retained it may be necessary to replace or relocate the door stops and to install additional fixings back to the structure. The joint between the frame and the surrounding structure should be adequately sealed and the operating gap between the door and the frame should be kept to a minimum (usually 3-4mm).

Part M - Access to and use of buildings

The Department has commissioned some comparative testing of doors using these two standards. The conclusions of this work are that for the purposes of Item 2.d of Table B1(provisions for fire doors) of Approved Document B (Vol2), results from EN 81-58 tests can be accepted as equivalent to BS 476 part 22. In due course, the Department intends to publish the report from this work and amendments to the Approved Document necessary to meet the requirements of the Lifts Directive.

Many do accept this arrangement where they are satisfied that it will provide a sufficient level of protection to escape routes within dwellings. The Building Control Alliance Technical Guidance Note 9 provides further advice.

Increasing the period of fire resistance of the compartment walls between flats beyond that specified in the Approved Document is unlikely to have any significant impact on the safety of occupants of the building and would have no discernable benefit to persons in the flat where the fire has started.

It is estimated that the provision of a BS 9251 sprinkler system within a dwelling will reduce fire-related casualties by around 70%. Whilst it would be desirable to install such systems in all dwellings it was decided that it would only be reasonable to impose this on larger buildings.

This was following analysis of the costs and benefits in the research report: The effectiveness of sprinklers in residential premises and consideration of the increased hazards for fire-fighters and other persons associated with fires in tall buildings, as discussed in the Regulatory Impact Assessment: Changes to Part B (Fire Safety) of the Building Regulations 2000 (as amended) and Approved Document B.

The 30m trigger height is considered to be a logical provision which aligns with the provisions for sprinkler protection for other building uses.

There may be alternative fire suppression systems that could be used where it can be demonstrated that a similar level of performance as would be provided by a BS 9251 sprinkler system can be achieved.

Where water mist systems are proposed the guidance contained in the BRE publication An Independent Guide on Water Mist Systems for Residential Buildings may assist Building Control Bodies in assessing such systems.

Diagram 30a applies a more onerous standard than Diagram 30b, any combustible (including thermosetting) core panels should incorporate a band of material of limited combustibility 300mm wide centred over the wall.

However, an alternative approach might be to use a panel system which has been shown in a large-scale test to resist internal and external surface flaming and concealed burning.

In low-rise residential, office or assembly buildings to which Diagram 30b applies, panels with thermosetting cores can be used without any additional protection.

However, fire-stopping must be provided to seal the joint between the compartment wall and the underside of the panel. Any voids above the panel (such as where an additional roof covering is provided) should also be adequately fire-stopped.

No. Requirement B3(3) requires, where reasonably necessary, subdivision of the building with fire-resisting construction and/or the installation of a suitable automatic fire suppression system.

What is considered reasonable in any particular case will depend on the size and intended use of the building. In some cases, either sprinklers or compartment walls and floors will be necessary and other cases it may be necessary to provide both or neither. Guidance on where sprinklers should be provided is given the Approved Document.

Door closers are not required for internal fire doors in flats when they are being used to provide lobby protection for a common stair.

However, the requirement for the provision of fire-resisting doors remains as does the advice to householders that doors should be kept shut, especially at night.

Regulation 4 of the Building Regulations 2000 states that “building work” should comply with the applicable requirements contained in Schedule 1. Regulation 4(2)a then goes on to state that, “after the work is completed, the building as a whole should comply with the applicable requirements of Schedule 1 or, where the building did not previously comply with any such requirement, is no more unsatisfactory in relation to that requirement than before the work was carried out.”

Where an existing shop is extended such that the final floor area is greater than 2000m2 (whether it exceeded this value previously or not) then the building as a whole may be less satisfactory in relation to requirement B3(3) than before the work was carried out.

Therefore, the building would have to be either subdivided to limit the compartment size, fitted with sprinklers or some other solution would be necessary in order to satisfy regulation 4(2) in relation to requirement B3.

Regulation 4(2) must be judged against the requirements set out in Schedule 1 rather than the Approved Document. B3(3) requires sub-division of the building “to an extent appropriate” to its size and intended use and it may be that some buildings will still comply with B3(3) by virtue of its intended use even though they have been extended without further capitalisation.

This would be a matter for the designer and the relevant building control body to consider. However, any such proposal may result in the need to upgrade the specification of the sprinkler system and the duration of water supplies.

Provision of water supplies does not, on its own, reduce the physiological impact on firefighters of travelling long distances whilst carrying heavy equipment. Water from private hydrants may still need to be pumped before it can be used for firefighting.

Where it is proposed to adopt an alternative approach to meeting requirement B5 (Access and facilities for the fire service). It would be advisable to seek the advice of the fire and rescue service who can advise on the practicalities of fire fighting.

The vertical distance referred to in paragraph 2.16 c. should be measured from the entrance storey of the flat, not the entrance floor of the building.

Item 2 of Table 3 (Maximum nominal internal diameter of pipes passing through fire separating element) now makes it clear that a uPVC pipe, up to 110mm in diameter, can pass through a wall or floor separating a dwellinghouse from an integral garage. The pipe should, however, still be fire stopped in accordance with paragraph 7.8. This would involve sealing around the pipe where it penetrates the wall or floor using a suitable material or a proprietary system as described in Paragraph 7.14.

Guidance in both volumes of the Approved Document Part B states there should be vehicle access for a pump appliance to within 45m of all points within dwellings. This is to take account of the actual distance that the Fire & Rescue Service need to carry kit and lay hoses from the vehicle to a potential point of fire.

Guidance in both Volumes of the Approved Document Part B states there should be vehicle access for a pump appliance to within 45m of all points within dwellings. This is to take account of the actual distance that the fire fighters need to carry kit and lay hoses from the vehicle to reach a potential fire.

When an Approved Document refers to a named standard, the relevant version of the standard is the one listed at the end of the publication. However, if this version of the standard has been revised or updated by the issuing standards body, the new version may be used as a source of guidance provided it continues to address the relevant requirements of the Regulations.

Volume 2 of Approved Document B currently refers to the guidance in several of the BS 5588 series of standards as a means of showing compliance with the requirements of Part B (Fire safety) of Schedule 1 to the Building Regulations. Until such time as the Approved Document is amended, these references remain part of the guidance approved under section 6 of the 1984 Building Act. As such, compliance with the guidance referred to would confer a legal presumption of conformity with the relevant requirements of Part B.
Following any other guidance would not confer that legal presumption.

Where designers elect to follow the relevant guidance in BS 9999 they will need to satisfy themselves and the building control body that this guidance adequately addresses the requirements of Part B. It is strongly recommended in such cases that designers discuss their proposals with the building control body before starting work.

Withdrawn BS standards are readily available from:
The BSI Knowledge Centre
British Standards Institution
389 Chiswick High Road
London, W4 4AL
Email: knowledgecentre@bsigroup.com
Tel: +44 (0)20 8996 7004

The Housing Act 2004 replaced the previous housing fitness standard with a statutory framework for assessing and tackling hazards in housing – including fire hazards.

Within a house designated as a ‘House in Multiple Occupation’ such devices may still need to be provided between the private areas (ie bedrooms) and the common parts (ie circulation spaces, living room, kitchen etc).

No, this is a printing error. The word “over” should be retained as for the 2000 edition of Approved Document Part B, and so paragraph 9.12 of Volume 2 of Approved Document Part B 2006 should read: “Where the concealed space is over an undivided area which exceeds 40m (this may be in both directions on plan) there is no limit to the size of the cavity if…….”.

Cavity barriers are provided to reduce the risk from unseen fire spread within concealed spaces in accordance with requirement B3(4) of the Building Regulations. The principle of paragraph 9.12 is that it relates to a concealed space over a single undivided room (such as an open-plan office). Because the room below the space is undivided, the occupants will be able to see a fire develop and react to the changing hazard, thus cavity barriers within the space above are less important than with a cellular layout. The conditions in paragraph 9.12 are intended to reduce the risk of a fire starting/spreading in the undivided void and to prevent fire entering the void from outside the room which is not visible to its occupants.

For the purposes of Part B of the Building Regulations an LD3 system is considered to be adequate. The system itself should therefore be installed in accordance with the guidance for LD3 systems in BS 5839-6:2004.

For the purposes of Part B of the Building Regulations, an LD3 system is considered to be adequate. The system itself should, therefore, be installed in accordance with the guidance for LD3 systems in BS 5839- 6: 2004.

For the purposes of meeting the provisions of Paragraph 8.14, the limit on the scope of BS 9251 to buildings below 20m can be ignored. However, the other limits such as the number of sprinkler heads per room should be observed.

In blocks which are taller than 30m in height, all the individual flats throughout the building should be sprinklered. However, it would not be necessary to provide them in the common areas such as stairs, corridors or landings.

The guidance in B1 Section 1 of the Approved Document (fire alarm and fire detection systems) is not intended to be applied to the common parts of blocks of flats and does not include a provision to interconnect installations in separate flats.

Fire detection devices may need to be provided in some blocks to actuate automatic smoke control systems in the common parts of the building in accordance with paragraph 2.25. Such devices are not expected to be linked to a common alarm system.

A protected stairway should be enclosed with fire-resisting construction and fire resisting doors in order to protect people escaping down the stairs from a fire in the accommodation.

It may not always be necessary to provide fire doors on cupboards if they are small and the fire risk is low. An alternative to providing a fire door on a bathroom is to include the bathroom within the stair enclosure, thus removing the need for a fire door.

In many cases, premises which are similar to a family home can be designed in accordance with Volume 1 (Dwelling houses). However, such premises are subject to the Regulatory Reform (Fire Safety) Order 2005 and it may be necessary to take account of the duties imposed under that Order in the design of the premises.

The Department’s leaflet, Do You Have Paying Guests? provides some useful guidance on the application of the Fire Safety Order to B&Bs, guest houses and self-catering properties. Regardless of the design guidance that is adopted, it will still be necessary for Building Control Bodies to consult with Fire and Rescue Authorities on work relating to buildings where the Fire Safety Order is (or will be) applicable. This should ensure that any potential problems can be identified before building work is started.

Further guidance on the consultation process is given in the Department’s publication, Building Regulations and Fire Safety Procedural Guidance.

Our local Fire and Rescue Service appliances are fitted with hoses which are much longer than 45m.
The 45m criterion is based on the physiological demands on firefighters engaged in search and rescue and on the restrictions that may be imposed by their equipment.

When considering hose length it is important to appreciate that, in practice, hoses have a tendency to “snake” when charged thus limiting their effective length. It is also common practice to trim the ends of hoses where they become damaged. The time and effort it takes to lay out a hose may also be an important factor.

A fire-resisting door should be regarded as a complete installed assembly. Thus the door, the frame and any ironmongery should be considered when assessing its suitability. In most cases, however, it should be possible to retain the existing frame. If in doubt, the test report for the door being installed will include details of the door frame in which it was tested.

Fire doors are often thicker and much heavier than other internal doors. Where existing frames are retained it may be necessary to replace or relocate the door stops and to install additional fixings back to the structure. The joint between the frame and the surrounding structure should be adequately sealed and the operating gap between the door and the frame should be kept to a minimum (usually 3-4mm).

Case Studies

All Building Control is London based and nationwide, some of our areas include...

All Building Control is London based and nationwide, some of our areas include...

Book a Site Inspection

*Due to the events of last year our services are taking slightly longer, we appreciate your patience.

Declaration and Request for Final Certificate by Client, Principal Designer, and Principal Contractor

1) I/we confirm that I/we have fulfilled our obligations in respect of Principal Designer / Principal Contractor as defined in Regulation 16E of The Building (Approved Inspector etc.) Regulations 2010 and Part 2A (duty holders and competence) of the Building Regulations 2010 (as amended). As far as I/we are reasonably and practicably able to ascertain, the works, to the best of our knowledge, comply with the Building Regulations. I/we therefore formally request issue of the Final Certificate.

2) I/we confirm that as the person carrying out the work, I/we have passed all pertinent fire safety information to the responsible person (RP) as required by Regulation 38 of the Building Regulations such that they may adequately and reasonably fulfil their ongoing obligation under the RR(FS)O.

    I am the:

    Date Appointed:

    Upload Signature: